- Indoor Air quality related to occupancy at an air-conditioned public building
- Universidade Estadual Paulista (UNESP)
- 1516-8913
- Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)
- Fundação para o Desenvolvimento da UNESP (FUNDUNESP)
- Com o objetivo de caracterizar a influência da ocupação na qualidade do ar interior, um edifício público com sistema de ar condicionado foi selecionado. As variáveis ambientais consideradas incluíram contagem total de bactérias e fungos, temperatura, umidade relativa e concentração de dióxido de carbono. O número de ocupantes, que variou durante todo o dia, foi estimado em cada amostragem. As amostras foram coletadas antes do início do expediente de trabalho e durante 3 horas, em intervalos de 30 minutos, por 5 dias úteis consecutivos. A análise de correlação demonstrou que a taxa de ocupação foi correlacionada positivamente com a concentração de bactérias, dióxido de carbono e temperatura. Nenhuma associação significativa foi observada entre o número de ocupantes e concentração de fungos. Os resultados deste estudo fornecem informações quanto à variabilidade nos parâmetros do ar interior no decorrer do dia em um edifício onde a ocupação é dinâmica.
- To characterize the influence of occupancy on the indoor air quality, a public office building with air-conditioning system was selected for this study. The indoor parameters included total bacteria count, total fungal count, temperature, relative humidity, and carbon dioxide concentration. The number of occupants, which varied throughout the day, was recorded in each sample. The samples were taken before the beginning of the working day and during 3 h, at an interval of 30 min between each sampling, and continued for five working days during a week. Correlation analysis demonstrated that occupancy rates were positively correlated with airborne bacteria, CO2, and temperature. No significant association between the number of occupants and fungus was observed. The results of this study provided information on the variability of indoor air parameters during the time-varying occupancy over the course of the day in at air-conditioned buildings where occupancy was quite dynamic.
- 1-Feb-2010
- Brazilian Archives of Biology and Technology. Brazilian Archives of Biology and Technology, v. 53, n. 1, p. 99-103, 2010.
- 99-103
- Brazilian Archives of Biology and Technology
- Indoor air quality
- air-conditioned
- occupancy
- office building
- http://dx.doi.org/10.1590/S1516-89132010000100013