You are in the accessibility menu

Please use this identifier to cite or link to this item: http://acervodigital.unesp.br/handle/11449/9843
Title: 
Corona Discharge Model for Transmission Lines by Lumped Elements
Author(s): 
Institution: 
  • Universidade Estadual de Campinas (UNICAMP)
  • Universidade Estadual Paulista (UNESP)
ISSN: 
1548-0992
Abstract: 
This paper shows the insertion of corona effect in a transmission line model based on lumped elements. The development is performed considering a frequency-dependent line representation by cascade of pi sections and state equations. Hence, the detailed profile of currents and voltages along the line, described from a non-homogeneous system of differential equations, can be obtained directly in time domain applying numerical or analytic solution integration methods. The corona discharge model is also based on lumped elements and is implemented from the well-know Skilling-Umoto Model.
Issue Date: 
1-Mar-2011
Citation: 
IEEE Latin America Transactions. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc, v. 9, n. 1, p. 804-809, 2011.
Time Duration: 
804-809
Publisher: 
Institute of Electrical and Electronics Engineers (IEEE)
Keywords: 
  • Corona discharge
  • lumped elements
  • transmission line model
  • state equations
Source: 
http://dx.doi.org/10.1109/TLA.2011.5876423
URI: 
Access Rights: 
Acesso restrito
Type: 
outro
Source:
http://repositorio.unesp.br/handle/11449/9843
Appears in Collections:Artigos, TCCs, Teses e Dissertações da Unesp

There are no files associated with this item.
 