You are in the accessibility menu

Please use this identifier to cite or link to this item: http://acervodigital.unesp.br/handle/11449/29078
Title: 
Distribution transformers modeling with angular displacement: actual values and per unit analysis
Author(s): 
Institution: 
  • Universidad Tecnológica de Pereira
  • Universidade Estadual Paulista (UNESP)
  • University of Edinburgh
ISSN: 
0103-1759
Abstract: 
In this work a detailed modeling of three-phase distribution transformers aimed at complementing well-known approaches is presented. Thus, incidence of angular displacement and tapping is taken into account in the proposed models, considering both actual values and per unit. The analysis is based on minimal data requirement: solely short-circuit admittance is needed since three-phase transformers are treated as non-magnetically-coupled single-phase transformers. In order to support the proposed methodology, results obtained through laboratory tests are presented.
Issue Date: 
1-Dec-2007
Citation: 
Sba: Controle & Automação Sociedade Brasileira de Automatica. Sociedade Brasileira de Automática, v. 18, n. 4, p. 490-500, 2007.
Time Duration: 
490-500
Publisher: 
Sociedade Brasileira de Automática
Keywords: 
  • Transformer modeling
  • angular displacement
  • distribution systems
Source: 
http://dx.doi.org/10.1590/S0103-17592007000400009