Please use this identifier to cite or link to this item:
http://acervodigital.unesp.br/handle/11449/72008
- Title:
- Test results of fault current limiter using YBCO tapes with shunt protection
- Universidade de São Paulo (USP)
- Universidade Estadual Paulista (UNESP)
- Universidade Estadual de Campinas (UNICAMP)
- 1742-6588
- 1742-6596
- A Fault Current Limiter (FCL) based on high temperature superconducting elements with four tapes in parallel were designed and tested in 220 V line for a fault current peak between 1 kA to 4 kA. The elements employed second generation (2G) HTS tapes of YBCO coated conductor with stainless steel reinforcement. The tapes were electrically connected in parallel with effective length of 0.4 m per element (16 elements connected in series) constituting a single-phase unit. The FCL performance was evaluated through over-current tests and its recovery characteristics under load current were analyzed using optimized value of the shunt protection. The projected limiting ratio achieved a factor higher than 4 during fault of 5 cycles without degradation. Construction details and further test results will be shown in the paper. © 2010 IOP Publishing Ltd.
- 1-Dec-2010
- Journal of Physics: Conference Series, v. 234, n. PART 3, 2010.
- Effective length
- Fault currents
- Fault-current limiter
- High temperature superconducting
- HTS tapes
- Load currents
- Over current
- Second generation (2G)
- Stainless steel reinforcement
- Test results
- YBCO coated conductors
- YBCO tape
- Critical current density (superconductivity)
- Electric fault currents
- High temperature superconductors
- Limiters
- Stainless steel
- Superconductivity
- Yttrium barium copper oxides
- Superconducting tapes
- http://dx.doi.org/10.1088/1742-6596/234/3/032002
- Acesso restrito
- outro
- http://repositorio.unesp.br/handle/11449/72008
There are no files associated with this item.
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.