Please use this identifier to cite or link to this item:
http://acervodigital.unesp.br/handle/11449/9679
- Title:
- Modal transformation analyses for double three-phase transmission lines
- Universidade Estadual Paulista (UNESP)
- Universidade Estadual de Campinas (UNICAMP)
- 0885-8977
- Eigenvector and eigenvalue analyses are carried out for double three-phase transmission lines, studying the application of a constant and real phase-mode transformation matrix and the errors of this application to mode line models. Employing some line transposition types, exact results are obtained with a single real transformation matrix based on Clarke's matrix and line geometrical characteristics. It is shown that the proposed technique leads to insignificant errors when a nontransposed case is considered. For both cases, transposed and nontransposed, the access to the electrical values (voltage and current, for example) is provided through a simple matrix multiplication without convolution methods. Using this facility, an interesting model for transmission line analysis is obtained even though the nontransposed case errors are not eliminated. The main advantages of the model are related to the transformation matrix: single, real, frequency independent, and identical for voltage and current.
- 1-Jul-2007
- IEEE Transactions on Power Delivery. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc., v. 22, n. 3, p. 1926-1936, 2007.
- 1926-1936
- Institute of Electrical and Electronics Engineers (IEEE)
- Clarke's matrix
- eigenvalue
- eigenvector
- frequency
- mode domain
- transformation matrix
- transmission lines
- http://dx.doi.org/10.1109/TPWRD.2007.899769