dc.identifier.citationPUPIN, Carlos Eduardo. Estudo da estabilidade a pequenas perturbações de sistemas elétricos multimáquinas com dispositivos FACTS do tipo SSSC e controladores suplementares (POD e PSS). 2009.. 144 f. Dissertação (mestrado) - Universidade Estadual Paulista, Faculdade de Engenharia de Ilha Solteira, 2009..-
dc.identifier.urihttp://hdl.handle.net/11449/87113-
dc.identifier.urihttp://acervodigital.unesp.br/handle/11449/87113-
dc.description.abstractEste trabalho apresenta estudos referentes à estabilidade a pequenas perturbações do sistema elétrico de potência, considerando a atuação de FACTS para o amortecimento das oscilações eletromecânicas de baixa freqüência. É abordado o dispositivo FACTS SSSC (Static Synchronous Series Compensator). Para este fim o sistema elétrico é modelado, modificando-se o Modelo de Sensibilidade de Potência para se inserir o compensador. Para melhorar a estabilidade do sistema desenvolvido, controladores são propostos para maximizar o desempenho do dispositivo SSSC, e dessa forma introduzir amortecimento ao sistema elétrico. Acrescenta-se ao modelo desenvolvido os Estabilizadores de Sistemas de Potência (ESP ou PSS – Power System Stabilizers) e o Power Oscillation Damping (POD), para atuação conjunta com o SSSC. Utilizando os fatores de participação e teoria de resíduos é possível encontrar a melhor localização para instalação dos dispositivos e realizar o ajuste dos parâmetros dos controladores. Simulações são realizadas para dois sistemas teste; um de quatro e outro de dez geradores. A partir dos resultados obtidos conclui-se pela potencialidade da utilização do SSSC para a melhoria da estabilidade a pequenas perturbações do sistema elétrico de potência.pt
dc.description.abstractThis work presents studies to provide damping to low frequencies oscillations of the electrical power systems by FACTS devices, considering SSSC (Static Synchronous Series Compensator). This is developed and implemented using the Power Sensitivity Model for multimachine systems. Afterwards, the SSSC devices are introduced as well as the controllers. The PSS (Power Systems Stabilizers) and POD (Power Oscillation Damping) controllers has been included using the participation factor and residue number theory to examine their best allocation on the electrical power systems. The study is based on modal analysis and time domain simulations using two test systems: four and ten generators. The simulation results show the capability of this method for small signal stability improvement for the electric power systems.en
dc.description.sponsorshipCoordenação de Aperfeiçoamento de Pessoal de Nível Superior (CAPES)-
dc.format.extent144 f. : il.-
dc.language.isopor-
dc.publisherUniversidade Estadual Paulista (UNESP)-
dc.sourceAleph-
dc.subjectSistemas de energia eletrica - Estabilidadept
dc.subjectOscilações eletromecânicaspt
dc.subjectElectric power systemsen
dc.subjectSmall signal stabilityen
dc.subjectElectromechanical oscillationsen
dc.titleEstudo da estabilidade a pequenas perturbações de sistemas elétricos multimáquinas com dispositivos FACTS do tipo SSSC e controladores suplementares (POD e PSS)pt
dc.typeoutro-
dc.contributor.institutionUniversidade Estadual Paulista (UNESP)-
dc.rights.accessRightsAcesso aberto-
dc.identifier.filepupin_ce_me_ilha.pdf-
dc.identifier.aleph000593631-
dc.identifier.capes33004099080P0-
Appears in Collections:Artigos, TCCs, Teses e Dissertações da Unesp

There are no files associated with this item.
 

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.